Cooling industries areas
Intercooler Type "F" : air outlet at the frontside
Intercooler Type "T" : air outlet at the top
A powerful fan sucks the air in, through the humidified pads. The air, leaving the unit, is humidified, cooled and filtered.
Characteristics
- Fan capacity: 1.200 Watt
- Air suction: 14.000 m³/h
- Fan diameter: 75 cm
- Pump capacity: 75 Watt
- Empty mass: 80 kg
- Water contents: 300 l
- Dimensions:
100 x 120 x 152 cm (type F)
100 x 120 x 215 cm (type T)
Example: determination of the cool:
Air is sucked in at a temperature of 40 ° C and an RH of 30%, the unit exits at a temperature of 28°C.
Temperature of the suction air |
%RH |
||||
15 | 30 | 40 | 50 | 60 | |
Temperature of the ejected air | |||||
25 | 15 | 17 | 18.5 | 20 | 21 |
30 | 18 | 20 | 22 | 24 | 25 |
35 | 21 | 24 | 26 | 28 | 30 |
40 | 25 | 28 | 31 | 33 | 34 |
45 | 28 | 32.5 | 35 | 37 | 39 |
50 | 32 | 36.5 | 39 | 41 | 43.5 |
click picture for detail pressure drop | |
click picture for detail indoor/outdoor temp |