Cooling industries areas



Intercooler Type "F" : air outlet at the frontside
Intercooler Type "T" : air outlet at the top

 

A powerful fan sucks the air in, through the humidified pads. The air, leaving the unit, is humidified, cooled and filtered.

 

 

Characteristics

  • Fan capacity: 1.200 Watt
  • Air suction: 14.000 m³/h
  • Fan diameter: 75 cm
  • Pump capacity: 75 Watt
  • Empty mass: 80 kg
  • Water contents: 300 l
  • Dimensions: 
    100 x 120 x 152 cm (type F)
    100 x 120 x  215 cm (type T)

 

 

Example: determination of the cool:

Air is sucked in at a temperature of 40 ° C and an RH of 30%, the unit exits at a temperature of 28°C.

 

 

Temperature of the suction air

%RH

  15 30 40 50 60
  Temperature of the ejected air
25 15 17 18.5 20 21
30 18 20 22 24 25
35 21 24 26 28 30
40 25 28 31 33 34
45 28 32.5 35 37 39
50 32 36.5 39 41 43.5

 

 

click picture for detail pressure drop
click picture for detail indoor/outdoor temp